Hi Smart, |
Thank you for choosing Bulldog Professional Inspection Services. I hope you found the experience both educational and insightful.
Let us know if you have any questions after reading your report.
We'll follow up in a few days to make sure you received it without trouble and have no last-minute questions.
It was our pleasure serving you and congratulations on your new home! |
Your summaries and report follow below. |
Steve Rodriguez President and Certified Master Inspector Bulldog Professional Inspection Services |
|
|
Client |
Property Address |
2.4 | EXTERIOR DOORS | |
Safety Item. | ||
11260/11258/11266 - Patio has big step into home. Maximum height should be 8" (step is currently 12" high). Recommend adding
intermediate step to avoid associated tripping hazard.
2.4 Item 1(Picture) - Large step into 11260
2.4 Item 2(Picture) - Large step into 11258
2.4 Item 3(Picture) - Large step into 11266
|
6.9 | SMOKE DETECTOR | |
Safety Item. | ||
11262/11266/11264/11260 - Smoke detectors missing in ALL bedrooms. Installation necessary to provide necessary early fire/smoke detection to spaces.
|
8.8 | SMOKE/CO DETECTORS | |
Safety Item. | ||
11258/11256 - Smoke detector missing in upstairs hallway. Installation necessary to provide necessary early fire/smoke detection to space.
|
9.7 | RECEPTACLES AND SWITCHES | |
Safety Item. | ||
11264/11260/11256 - No GFCI protection to the left of sink. Recommend installing to provide necessary electrical safety protection to circuit.
|
12.0 | BASEMENT STAIRWAY AND RAILING | |
Safety Item. | ||
11264 - Missing handrail at basement steps. Recommend installing to provide necessary stability during use.
12.0 Item 1(Picture) - Missing handrail at 11264 basement steps
|
12.12 | SMOKE / CO DETECTORS | |
Safety Item. | ||
11256 - Smoke detector missing. Installation necessary to provide necessary early fire/smoke detection to space.
|
14.4 | CHIMNEYS, FLUES AND VENTS | |
Maintenance Item. | ||
(3) 11266 - Open seams at HVAC exhaust vent above furnace. This is a health hazard since dangerous flue gases can escape into home.
Recommend properly sealing all open seams with metal tape to maximize draw and maintain safe furnace operation.
14.4 Item 3(Picture) - Open seams at 11266 furnace exhaust vent
|
14.7 | SMOKE/CO DETECTORS IN SPACE | |
Safety Item. | ||
11262/11266/11264/11260/11258/11256 - No CO detector present in rooms with fuel burning appliances. A CO detector should be installed in same space as all fuel-burning appliances (not directly above or beside units since it is normal for them to emit a small amount of carbon monoxide upon start-up) and in all upper-level hallways. Recommend installing to provide early CO detection to occupants and avoid associated personal safety hazards
|
Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Steve Rodriguez
|
Client |
Property Address |
3.0 | COMPRESSOR UNIT | |
Specialist Item. | ||
(1) 11256/11262/11264/11266 - Outdoor unit is not level. Excessive movement can crack HP/LP tubing at connections. Unit works as intended
during time of inspection, but recommend bringing unit to within 1 inch of level to maintain proper performance.
3.0 Item 1(Picture) - 11256 condenser unit not level
3.0 Item 2(Picture) - 11262 condenser not level
3.0 Item 3(Picture) - 11264 condenser is not level
3.0 Item 4(Picture) - 11266 A/C condenser is not level
|
||
(4) 11262/11264 - Broken electrical conduit at condenser unit. This makes wiring vulnerable to inadvertent damage. Recommend contracting
professional HVAC technician to repair to maintain associate safe and proper performance. Unit operates properly during time of inspection.
3.0 Item 7(Picture) - Broken conduit at 11262 A/C
3.0 Item 8(Picture) - Broken conduit at 11264 A/C unit
|
||
(6) 11264 - Damaged fins at exterior condenser unit. Recommend contracting licensed HVAC technician to repair to maintain proper condenser
performance. Unit operates properly during time of inspection.
3.0 Item 9(Picture) - Dirty fins at 11264 condenser unit
|
3.1 | REFRIGERANT LINES | |
Specialist Item. | ||
(1) 11258 - A/C refrigerant lines have iced up at condenser. This is often caused by low refrigerant, a clogged filter, or a clogged evaporator
coil. Recommend contracting professional HVAC contractor to evaluate and repair to maintain proper system performance. A/C is blowing
warm during time of inspection.
3.1 Item 1(Picture) - Refrigerant lines have iced up
|
3.2 | EVAPORATOR UNIT | |
Specialist Item. | ||
(1) 11258 - Evaporator is actively leaking behind furnace enclosure. This is often caused by cracked pan or clogged drain. If left unattended,
this condition may ultimately crack the heat exchanger and cause premature furnace replacement. Recommend contracting licensed HVAC
technician to repair to maximize remaining life and system performance. No significant damages visible during time of inspection.
3.2 Item 1(Picture) - 11258 evaporator is leaking behind furnace
|
||
(2) 11256 - Evaporator is actively leaking on top of furnace enclosure. This is often caused by cracked pan or clogged drain. If left unattended,
this condition may ultimately crack the heat exchanger and cause premature furnace replacement. Recommend contracting licensed HVAC
technician to repair to maximize remaining life and system performance. No significant damages visible during time of inspection.
3.2 Item 2(Picture) - Evaporator leakage on top of 11256
|
7.6 | LIGHTING | |
Specialist Item. | ||
(1) 11262/11260 - Lighting is on GFCI circuit in main floor half bath. This is improper since lights will not work if GFCI circuit is tripped. Recommend contracting professional electrician to place lights on dedicated circuit to maintain constant, reliable function.
|
9.2 | CEILING | |
Specialist Item. | ||
11262 - Moisture stains and damages visible at ceiling. This appears to be caused from active leakage at toilet in hall bath, above.
Recommend hiring professional roofing contractor to investigate and repair to avoid continued moisture damages. Unable to determine
extent of underlying damages during time of inspection.
9.2 Item 1(Picture) - Active leakage in 11262 kitchen ceiling
|
12.2 | FOUNDATION / WALLS | |
Specialist Item. | ||
(1) 11266 - Settlement cracking visible on East side of basement. Previous repairs do not appear to have been successful since subsequent
movement is visible. Recommend hiring professional foundation contractor to properly repoint to avoid further deterioration and possible
moisture seepage. None visible during time of inspection.
12.2 Item 1(Picture) - Settlement crack in 11266 foundation wall
|
12.3 | CEILING / SUB-FLOOR | |
Specialist Item. | ||
(1) 11260 - Moisture damages visible at sub-floor beneath half bath toilet. Recommend hiring professional contractor to evaluate and repair to
avoid further leakage and associated damages. No significant damages visible during time of inspection.
12.3 Item 1(Picture) - Active leakage beneath 11260 half bath toilet
|
||
(2) 11260 - Daylight visible through sub floor on South side of basement. Recommend hiring professional contractor to investigate and repair to
avoid continued damage to underlying framing members. No significant damages visible during time of inspection.
12.3 Item 2(Picture) - Daylight through 11260 rim joist
|
14.1 | HEATING EQUIPMENT | |
Maintenance Item. | ||
(2) 11258 - Furnace is 37 years old (expected life is 20-25 years) and displays heavy rust, corrosion, and sediment build-up in
burner/blower/heat exchanger areas. Unable to determine extent of underlying damages, but unit performs as intended during time of
inspection. Recommend having unit serviced regularly to maximize life and system efficiency. Budget for future replacement.
14.1 Item 4(Picture) - View inside 11258 furnace
|
15.0 | MAIN WATER SUPPLY | |
Specialist Item. | ||
11256 - Active leakage in pressure reducing valve. Recommend contracting plumber to evaluate and repair to avoid continued leakage and
possible moisture damage. None visible during time of inspection.
15.0 Item 1(Picture) - Active leak at 11256 pressure reducing valve
|
15.3 | DISTRIBUTION PIPING | |
Specialist Item. | ||
11262 - Copper plumbing is in contact with galvanized HVAC ducting. This will lead to galvanic corrosion and leakage. Recommend
contracting professional plumber to evaluate and relocate to avoid possible moisture damages. None visible during time of inspection.
15.3 Item 1(Picture) - Water lines touch galvanized ducting in 11262 basement
|
15.5 | FUEL DISTRIBUTION SYSTEMS | |
Specialist Item. | ||
11260 - No dirt leg present on natural gas supply line to water heater. This is piping component is necessary to keep natural gas clean and
extend life of associated gas appliances. Recommend installing to maximize useful life. See attached photo at bottom of report for a
detailed view.
15.5 Item 1(Picture) - No dirt leg at 11260 water heater
|
15.6 | WATER HEATER | |
Maintenance Item. | ||
(3) 11262 - Glass view port is broken. This will affect water heater efficiency and performance. Recommend hiring professional plumber to
evaluate and repair to restore safe and proper operation.
15.6 Item 8(Picture) - Broken glass at 11262 water heater
|
16.0 | SERVICE ENTRANCE | |
Specialist Item. | ||
11256/11260 - Electrical service meter is pulling away from home. This is likely caused by grading settlement. Recommend contract local
utility to properly evaluate and repair to maintain reliable service and avoid possible damage. No significant damages visible during time of
inspection.
16.0 Item 1(Picture) - Loose meter at 11256
16.0 Item 2(Picture) - Loose meter at 11260
|
16.1 | DISTRIBUTION PANEL | |
Maintenance Item. | ||
(2) 11262 - 15-Amp circuit breaker in main panel would not reset (unable to turn breaker on) during time of inspection. Recommend contracting
electrician to investigate and repair to restore proper operation. Unable to pinpoint cause during time of inspection.
16.1 Item 2(Picture) - Breaker will not reset in 11262 panel
|
||
(4) 11264/11256 - Double tapping present (2 circuits double tapped). This presents a possible overheating hazard. Contract professional
electrician to evaluate and correct to avoid associated electrical safety hazards and maintain proper system performance. No associated
damages visible during time of inspection.
16.1 Item 5(Picture) - Double tapped breaker inside 11264 panel
16.1 Item 6(Picture) - Double tapped breaker inside 11256 panel
|
16.3 | GROUNDING | |
Specialist Item. | ||
11266/11260/11256 - No main grounding conductor installed. Installation necessary to maintain electrical grounding protection to home. Contract licensed electrician to properly correct and restore electrical safety to system and occupants.
|
Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Steve Rodriguez
|
Client |
Property Address |
1.0 | LANDSCAPING AND DRAINAGE | |
Maintenance Item. | ||
Landscaping is flat and slopes toward building at various areas actions building. This is a typical condition found in many properties.
Recommend sloping grading away from building 1" per foot out to 6 feet to provide proper drainage and reduce possible foundation shifting
(85-90% of all foundation moisture problems can be avoided with proper grading and downspout extensions). None visible during time of
inspection.
1.0 Item 1(Picture) - Landscaping slopes toward building on East side
1.0 Item 2(Picture) - Landscaping slopes toward building at NW corner
1.0 Item 3(Picture) - Landscaping slopes toward building at SW corner
|
1.1 | DRIVEWAY AND PARKING LOT | |
Maintenance Item. | ||
Driveway has cracked and deteriorated to a point where it creates a trip hazard. . Recommend hiring professional driveway contractor to
evaluate and repair to avoid continued deterioration and future personal injury.
1.1 Item 1(Picture) - Worn and deteriorated asphalt in parking lot
|
1.2 | WALKWAY | |
Maintenance Item. | ||
11256 - Open space beneath walkway due to grading settlement. This does not pose an immediate structural issue, but recommend filling
space with concrete to avoid future movement and associated structural damages. None visible during time of inspection.
1.2 Item 1(Picture) - Space beneath 1256 walkway
|
1.4 | PATIO | |
Maintenance Item. | ||
(1) 11258/11260 - Patio slopes to the South. This is not structurally significant to home, but does make patio difficult to use. Recommend
careful mud jacking to correct and avoid continued movement. No associated structural damages visible during time of inspection.
1.4 Item 1(Picture) - 11258 patio slopes away from building
1.4 Item 2(Picture) - 11260 patio slopes away from building
|
||
(2) 11266 - Patio slopes toward home. This is caused by grading movement and is potentially damaging to foundation. Recommend hiring
professional patio contractor to evaluate and repair to avoid possible moisture seepage within basement. None visible during time of
inspection.
1.4 Item 3(Picture) - 11266 patio slopes toward foundation
|
2.1 | WALL SIDING, FLASHING, AND TRIM | |
Maintenance Item. | ||
(1) Exposed nails, peeling paint, and rot at siding and trim around building . Recommend properly repairing and repainting all damaged areas to
avoid continued damage and possible moisture penetration within underlying framing areas. Unable to determine if any underlying damages
exist during time of inspection.
2.1 Item 1(Picture) - Rot on East side of building
2.1 Item 2(Picture) - Other area of rot on East side of building
2.1 Item 3(Picture) - Rot above 11262 entryway
2.1 Item 4(Picture) - Rot at base of siding on East side
2.1 Item 5(Picture) - Rot at base of siding at 11260
2.1 Item 6(Picture) - Rot on West side of building
2.1 Item 7(Picture) - Rot behind trim on West side of building
2.1 Item 8(Picture) - Rot at SW corner of building
|
||
(2) Vegetation too close to siding around building. This will lead to premature siding wear, moisture problems within wall, and creates an easy
path for wood destroying insects to enter home. Recommend trimming back all vegetation at least 12" to avoid associated damages. None
visible during time of inspection.
2.1 Item 9(Picture) - Vegetation on East side
2.1 Item 10(Picture) - Vegetation at NE corner of building
|
||
(3) Ivy growth around building This crawls under siding and gets into home. . Recommend removing to reduce associated underlying damages.
None visible during time of inspection.
2.1 Item 11(Picture) - Ivy growth on West side of building
|
2.2 | WINDOWS | |
Maintenance Item. | ||
Peeling paint and rot at window frames and sills around building. Recommend properly repairing and repainting to avoid continued damage
to underlying framing areas. No underlying moisture damages visible during time of inspection.
2.2 Item 1(Picture) - Rot and peeling paint on East side of building
2.2 Item 2(Picture) - Rot and peeling paint at West side windows
|
3.0 | COMPRESSOR UNIT | |
Specialist Item. | ||
(2) 11256 - Outdoor unit is 18 years old, rusty, and nearing the end of its useful life. It operates as intended during time of inspection; however,
recommend servicing to maximize performance. Additionally, recommend providing annual system maintenance to maximize efficiency and
extend useful life. Budget for replacement.
3.0 Item 5(Picture) - 11256 condenser is 18 years old and rusty
|
||
(3) 11258 - Dirty fins at exterior condenser unit. Recommend cleaning (spray off with hose) to maximize life and efficiency. Unit operates
properly during time of inspection.
3.0 Item 6(Picture) - Dirty fins at 11258 condenser unit
|
||
(5) 11264 - Outdoor unit is approx. 30 years old, rusty, and nearing the end of its useful life. It operates as intended during time of inspection;
however, recommend servicing to maximize performance. Additionally, recommend providing annual system maintenance to maximize
efficiency and extend useful life. Budget to replace.
|
||
(7) 11266 - Soil has been built up around compressor unit. Recommend removing to avoid deterioration and associated damages. None visible
during time of inspection.
3.0 Item 10(Picture) - Soil up around 11266 A/C unit
|
||
(8) 11266 - Outdoor unit is damaged. It appears unit has been hit with lawn mower. Recommend repairing to maintain proper performance.
Unit operates properly during time of inspection.
3.0 Item 11(Picture) - 11266 A/C is damaged
|
3.1 | REFRIGERANT LINES | |
Specialist Item. | ||
(2) 11260/11262 - Worn and deteriorated insulation at A/C refrigerant line. This will lower overall efficiency of system. Recommend repairing to
ensure maximum efficiency.
3.1 Item 2(Picture) - Worn insulation at 11260 refrigerant lines
3.1 Item 3(Picture) - Missing insulation in at 11262
|
4.0 | GUTTERS, DOWNSPOUTS, AND DRAINAGE | |
Maintenance Item. | ||
Downspout drains water too close to foundation on East side of building. Recommend extending at least 6' away from foundation wall to
avoid possibility of moisture penetration and associated damages. None visible during time of inspection.
4.0 Item 1(Picture) - Extend downspout on East side
|
4.1 | SOFFITS AND FASCIAS | |
Maintenance Item. | ||
Peeling paint and rot soffit/fascia boards around building. Recommend properly repairing and repainting all damaged areas to extend their
useful life. No significant damages visible during time of inspection.
4.1 Item 1(Picture) - Peeling paint on East side
4.1 Item 2(Picture) - Peeling paint above 11260
4.1 Item 3(Picture) - Rot in soffit on West side
4.1 Item 4(Picture) - Hole in soffit at SW corner of roof
4.1 Item 5(Picture) - Rot and peeling paint on West side
4.1 Item 6(Picture) - Rot at 11264 Soffit on West side
4.1 Item 7(Picture) - Peeling paint and rot on South side
|
5.0 | ROOF STRUCTURE | |
Maintenance Item. | ||
11266 - Split roof rafter visible on South side of attic. This indicates possible point of weakness. Recommend properly repairing to maintain
designed weight bearing capacity to roof structure. No underlying structural damages visible during time of inspection.
5.0 Item 1(Picture) - Split roof rafter in 11266 attic
|
5.1 | INSULATION | |
Maintenance Item. | ||
11262 - 3 inches of blown fiberglass insulation present. U.S. Department of Energy recommends R-38 rating in attic spaces, which equates
to 13 inches. Consider providing additional depth to maintain intended energy efficiency to home and reduce associated fuel costs.
5.1 Item 1(Picture) - 3 inches of blown fiberglass insulation in all attics
|
6.3 | WINDOWS | |
Maintenance Item. | ||
(1) 11262 - Window missing latch on North bedroom. Recommend installing to provide intended security protection to home.
|
||
(2) 11262 - Window assist/lift components are not working properly in South bedroom (window will not stay up). Recommend repairing to restore proper window performance.
|
6.6 | LIGHTING | |
Maintenance Item. | ||
11266 - Light out. Replace bulb. If this does not correct, recommend contracting electrician to
investigate and correct to restore safe and proper operation.
|
7.1 | FLOOR | |
Maintenance Item. | ||
11260 - Missing caulking at base of tub enclosure. Recommend properly sealing to reduce possible moisture penetration and associated
damages. Floor is soft and slopes toward tub during time of inspection.
7.1 Item 1(Picture) - Missing caulking at 11260 floor
|
7.2 | WALLS | |
Maintenance Item. | ||
11266 - Superficial mold growth visible at upstairs bathroom wall, but no moisture detected during time of inspection. This appears to be
caused from active moisture leaks within bathroom. Recommend cleaning wall to avoid associated moisture damage. None visible during
time of inspection.
7.2 Item 1(Picture) - Superficial mold in 11266 bathroom wall
|
7.3 | CEILING | |
Maintenance Item. | ||
11264 - Old moisture stains visible at half bath ceiling, but no moisture detected during time of inspection. This appears to be caused from
overflow or leak at hall bath, above. Recommend properly sealing and painting to avoid future moisture damage. No underlying damages
visible during time of inspection.
7.3 Item 1(Picture) - Old moisture stains in 11264 half bath ceiling
|
7.6 | LIGHTING | |
Specialist Item. | ||
(2) 11264 - Light out in half bath. Replace bulb. If this does not correct, recommend contracting electrician to
investigate and correct to restore safe and proper operation.
|
7.9 | SINK, FAUCET, PLUMBING, AND TRAP DRAIN | |
Not Present., Maintenance Item. | ||
(1) 11262 - Active leakage at sink basin in upstairs bath. Recommend properly repairing to avoid further leakage and associated moisture
damages. No significant damages visible during time of inspection.
7.9 Item 1(Picture) - Leak at 11262 sink basin
|
||
(2) 11266 - Faucet leaks in upstairs bath. Recommend repairing to restore operation.
|
||
(3) 11264 - Faucet is loose in half bath. . Recommend properly securing to avoid any possible inadvertent piping damages during use. None
visible during time of inspection.
|
||
(4) 11260 - Active leakage beneath both sinks. Recommend properly repairing to avoid further leakage and associated moisture damages.
Moisture damages visible beneath left sink during time of inspection.
7.9 Item 2(Picture) - Active leak beneath both sink in 11260 upstairs bath
|
||
(5) Slow drain at left sink. Recommend cleaning to restore proper drainage. If this does not correct, contract plumber to investigate and repair
to avoid possible overflow. No associated damages visible during time of inspection.
|
7.11 | TOILET | |
Maintenance Item. | ||
(1) 11262 - Upstairs toilet is loose and leaking. Recommend properly repairing to avoid future damages to underlying framing members. Unable
to determine extent of underlying damages during time of inspection.
7.11 Item 1(Picture) - Leakage at 11262 upstairs toilet
|
||
(2) 11262/11266/12258 - Half bath toilet is loose. This condition will eventually worsen and leak if not repaired. Recommend properly securing
to avoid future leakage and associated damages. None visible during time of inspection.
|
||
(3) 11266/11264/11260/11258/11256 - Upstairs toilet is loose. This condition will eventually worsen and leak if not repaired. Recommend
properly securing to avoid future leakage and associated damages. None visible during time of inspection.
|
||
(4) 11264 - Toilet flush handle is broken in half bath. Recommend repairing to restore proper operation.
|
||
(5) 11260 - Half bath toilet is loose and leaking. Recommend properly repairing to avoid further leakage and associated moisture damages.
Unable to determine extent of underlying damages during time of inspection.
|
7.12 | TUB AND ENCLOSURE | |
Maintenance Item. | ||
(1) 11262 - Loose shower head piping and faucet in upstairs bath. Recommend properly securing to avoid possible leakage due to movement.
None visible during time of inspection.
|
||
(2) 11262 - Tub faucet is leaking. Recommend repairing to restore proper operation.
|
||
(3) 11264 - Deteriorated caulking at base of tub enclosure. Recommend properly recaulking to reduce possible moisture penetration and
associated damages. None visible during time of inspection.
7.12 Item 1(Picture) - Deteriorated caulking at base of 11264 tub enclosure
|
||
(4) 11260/11256 - Loose shower head piping. Recommend properly securing to avoid possible leakage due to movement. None visible during
time of inspection.
|
||
(5) 11258 - Faucet diverter is stuck closed (only shower works). Recommend repairing to restore proper operation.
|
8.7 | FRONT DOOR | |
Maintenance Item. | ||
11266 - Deteriorated weatherstripping around front door. Recommend repairing to reduce possible moisture penetration and increase energy
efficiency to space.
8.7 Item 1(Picture) - Deteriorated caulking around 11266 front door
|
9.8 | SINK, FAUCET, PLUMBING, AND TRAP DRAIN | |
Maintenance Item. | ||
11264 - Active leakage beneath sink. Recommend properly repairing to avoid further leakage and associated moisture damages. No
significant damages visible during time of inspection.
9.8 Item 1(Picture) - Active leakage beneath 11264 kitchen sink
|
9.13 | RANGE HOOD | |
Maintenance Item. | ||
11264/11260 - Light is out. Replace bulb. If this does not correct, recommend contracting electrician to investigate and repair as necessary to restore proper operation.
|
10.4 | PATIO DOOR | |
Maintenance Item. | ||
11266 - Active leakage around patio door. Recommend hiring professional contractor to evaluate and repair to maintain proper performance. Unable to determine extent of underlying damages during time of inspection.
|
11.4 | LIGHTING | |
Maintenance Item. | ||
11266 - Light out. Replace bulb. If this does not correct, recommend contracting electrician to
investigate and correct to restore safe and proper operation.
|
12.2 | FOUNDATION / WALLS | |
Specialist Item. | ||
(2) 11256 - Superficial mold visible on wall. This is likely due to basement bring dark and dryer venting into space. Recommend cleaning wall
and installing dehumidifier within basement to avoid associated health hazards. No moisture damages visible during time of inspection.
12.2 Item 2(Picture) - Mold on walls in 11256 basement
12.2 Item 3(Picture) - More mold in 11256 basement
12.2 Item 4(Picture) - And more superficial mold in 11256 basement
|
14.1 | HEATING EQUIPMENT | |
Maintenance Item. | ||
(1) 11262/11260/11256 - Furnace is 20 years old (expected life is 20-25 years) and displays heavy rust and corrosion in burner/heat exchanger
areas. Unable to determine extent of underlying damages, but unit performs as intended during time of inspection. Recommend having unit
serviced regularly to maximize life and system efficiency. Budget for future replacement.
14.1 Item 1(Picture) - Rust and corrosion in 11262 furnace
14.1 Item 2(Picture) - Rust and corrosion inside 11260 furnace
14.1 Item 3(Picture) - Rust and corrosion inside 11256 furnace
|
14.4 | CHIMNEYS, FLUES AND VENTS | |
Maintenance Item. | ||
(1) 11262 - HVAC supply vent is disconnected within basement. Recommend properly sealing with metallic tape to maximize system
efficiency.
14.4 Item 1(Picture) - Vent disconnected inside 11262 basement
|
||
(2) 11262 - Duct tape used to seal seams at HVAC vents. This is improper and tape will ultimately become dry and brittle. Recommend
properly sealing all open seams with metal tape then properly insulating ducting to maximize flow and efficiency to home.
14.4 Item 2(Picture) - Duct tape at vents in 11262 basement
|
14.8 | FURNACE ENCLOSURE | |
Maintenance Item. | ||
11262/11264/11260 - Air leaks at seams around furnace enclosure. This is inefficient. Recommend sealing all leaks with metallic tape to
maximize system efficiency and improve performance.
14.8 Item 1(Picture) - Air leaks around 11262 furnace enclosure
14.8 Item 2(Picture) - Air leaks around 11264 furnace enclosure
14.8 Item 3(Picture) - Air leak at 11260 refrigerant lines
|
15.1 | MAIN WATER SHUT-OFF | |
Maintenance Item. | ||
11262/11260 - Active leakage in water main valve. Recommend contracting professional plumber to evaluate and repair to avoid continued
leakage and possible moisture damage. None visible during time of inspection.
15.1 Item 1(Picture) - Active leakage at 11262 water main
15.1 Item 2(Picture) - Active leakage at 11260 water main
|
15.6 | WATER HEATER | |
Maintenance Item. | ||
(1) 11262/11266/11264/11260/11258/11256 - Active leakage at drip tube. This can be caused by high tank pressure or sediment beneath valve
seat. Recommend contracting professional plumber to evaluate and repair to restore proper performance. No associated damages visible
during time of inspection.
15.6 Item 1(Picture) - Active leak at 11262 water heater relief valve
15.6 Item 2(Picture) - Active leak at 11266 relief valve
15.6 Item 3(Picture) - Active leak at 11264 relief valve
15.6 Item 4(Picture) - Active leak at 11260 relief valve
15.6 Item 5(Picture) - Active leak at 11258 relief valve
|
||
(2) 11262/11258 - Rust and corrosion in and around water heater. Units are 13 & 8 years old and operate as intended during time of
inspection. These conditions and its age (typical life of water heater is 10-12 years) indicate unit is at the end of its useful life. Budget for
replacement.
15.6 Item 6(Picture) - Rust at base of 11262 water heater
15.6 Item 7(Picture) - Corrosion on top of 11258 water heater
|
||
(4) 11266 - Rust and corrosion in and around water heater. Unit is 17 years old and operates as intended during time of inspection. These
conditions and its age (typical life of water heater is 10-12 years) indicate unit is at the end of its useful life. Budget to replace.
15.6 Item 9(Picture) - Rust around 11266 water heater
|
||
(5) 11260 - Active leakage at drain bibb. Recommend hiring professional plumber to evaluate and repair to reduce continued leakage and
associated moisture damages. Moisture damages visible during time of inspection.
15.6 Item 10(Picture) - Active leakage at 11260 drain bibb
|
16.1 | DISTRIBUTION PANEL | |
Maintenance Item. | ||
(1) 11262/11266/11264/11260/11258/11256 - Zinsco main distribution panel installed. These panels were originally made in Puerto Rico and
installed in the 60's and 70's throughout the USA. There are many still in use in both single-family and multi-family units. Zinsco sold
their manufacturing plants to Sylvania who then marketed them under the GTE Sylvania brand until finally closing down. Today, the
Zinsco name is owned by Thomas and Betts.
Major Problems: 1) It has been found that circuit breakers do not trip under normal overload conditions (It has been known to sometimes take up to 60-amps to trip a 15-amp Zinsco breaker. 2) The parallel flat buss bars are made of aluminum material and corrode quite easily, increasing the electrical resistance at point of contact and causing panels to overheat. 3) The plating that coats the buss bars sometimes fails on many Zinsco panels, causing poor circuit breaker connections. 4) Another problem is that the breakers do not have designated positions, i.e., they can slide up and down the buss bar, are often crooked, and it is not uncommon to see gaps between the breakers with the deadfront cover in place. Recommend monitoring panel for signs of overheating. No signs of past problems visible during time of inspection. 16.1 Item 1(Picture) - This is a Zinsco panel
|
||
(3) 11262/11266 - Knockout missing. These are necessary to maintain designed electrical safety and avoid rodent intrusion. Recommend
contracting electrician to install and avoid associated electrical safety hazards.
16.1 Item 3(Picture) - Missing knockout at 11262 panel
16.1 Item 4(Picture) - Missing knockout at 11266 panel
|
||
(5) 11258 - Twistout missing. These are necessary to maintain designed electrical safety and avoid rodent intrusion. Recommend contracting
electrician to install and avoid associated electrical safety hazards.
16.1 Item 7(Picture) - Missing twistout in 11258 panel
|
Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Steve Rodriguez
This Page Begins Your Full Home Inspection Report
Date: 5/11/2021 | Time: 10:00 AM | Report ID: 20170605-6-unit-property |
Property: 6 Unit Property Kansas City MO 64137 |
Customer: Smart Investor |
Real Estate Professional: Great Agent |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor and all costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected. Good Or Working Condition. (IN) = The item, component or unit was visually observed and appeared sound or functioning as intended.
Not Inspected. (NI) = The item, component or unit was not inspected. However, in the interest of the client and whenever possible, stated observations are made based upon visually verifiable conditions or accessible areas. Please be aware that the nature of these observations prevent reporting on hidden areas with certainty.
Not Present. (NP) = This item, component or unit is not in this home or building.
Maintenance Item. (MN) = The item, component or unit appears deficient or needs repair or maintenance by homeowner or qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Major Item. (MJ) = The item, component or unit is deficient or needs further inspection, service or repair by a qualified/licensed contractor or qualified specialist. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Safety Item. (SI) = The item, component or unit is deficient and/or presents a safety hazard to the occupants and/or the dwelling. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Type Of Building: MULTI-FAMILY | Age Of Building: 44 | Occupancy: OCCUPIED |
Beds and Baths: 2 BED 1.5 BATH | Building Faces: EAST | Fire Hydrant: WITHIN 25 feet |
Termite Inspection: YES | Temperature: OVER 60 | Weather: CLEAR AND WARM |
Rain in last 3 days: YES |
Driveway:
ASPHALT |
Walkway:
CONCRETE |
Porch:
CONCRETE |
Patio:
CONCRETE |
1.0 |
LANDSCAPING AND DRAINAGE
Comments: Maintenance Item. |
Landscaping is flat and slopes toward building at various areas actions building. This is a typical condition found in many properties.
Recommend sloping grading away from building 1" per foot out to 6 feet to provide proper drainage and reduce possible foundation shifting
(85-90% of all foundation moisture problems can be avoided with proper grading and downspout extensions). None visible during time of
inspection.
1.0 Item 1(Picture) - Landscaping slopes toward building on East side
1.0 Item 2(Picture) - Landscaping slopes toward building at NW corner
1.0 Item 3(Picture) - Landscaping slopes toward building at SW corner
|
1.1 |
DRIVEWAY AND PARKING LOT
Comments: Maintenance Item. |
Driveway has cracked and deteriorated to a point where it creates a trip hazard. . Recommend hiring professional driveway contractor to
evaluate and repair to avoid continued deterioration and future personal injury.
1.1 Item 1(Picture) - Worn and deteriorated asphalt in parking lot
|
1.2 |
WALKWAY
Comments: Maintenance Item. |
11256 - Open space beneath walkway due to grading settlement. This does not pose an immediate structural issue, but recommend filling
space with concrete to avoid future movement and associated structural damages. None visible during time of inspection.
1.2 Item 1(Picture) - Space beneath 1256 walkway
|
1.3 |
PORCH
Comments: Inspected. Appears Good Or In Working Condition. |
1.4 |
PATIO
Comments: Maintenance Item. |
(1) 11258/11260 - Patio slopes to the South. This is not structurally significant to home, but does make patio difficult to use. Recommend
careful mud jacking to correct and avoid continued movement. No associated structural damages visible during time of inspection.
1.4 Item 1(Picture) - 11258 patio slopes away from building
1.4 Item 2(Picture) - 11260 patio slopes away from building
|
|
(2) 11266 - Patio slopes toward home. This is caused by grading movement and is potentially damaging to foundation. Recommend hiring
professional patio contractor to evaluate and repair to avoid possible moisture seepage within basement. None visible during time of
inspection.
1.4 Item 3(Picture) - 11266 patio slopes toward foundation
|
Foundation Walls:
POURED CONCRETE |
Siding Materials:
COMPOSITE BOARD |
2.0 |
EXTERIOR FOUNDATION WALLS
Comments: Inspected. Appears Good Or In Working Condition. |
2.1 |
WALL SIDING, FLASHING, AND TRIM
Comments: Maintenance Item. |
(1) Exposed nails, peeling paint, and rot at siding and trim around building . Recommend properly repairing and repainting all damaged areas to
avoid continued damage and possible moisture penetration within underlying framing areas. Unable to determine if any underlying damages
exist during time of inspection.
2.1 Item 1(Picture) - Rot on East side of building
2.1 Item 2(Picture) - Other area of rot on East side of building
2.1 Item 3(Picture) - Rot above 11262 entryway
2.1 Item 4(Picture) - Rot at base of siding on East side
2.1 Item 5(Picture) - Rot at base of siding at 11260
2.1 Item 6(Picture) - Rot on West side of building
2.1 Item 7(Picture) - Rot behind trim on West side of building
2.1 Item 8(Picture) - Rot at SW corner of building
|
|
(2) Vegetation too close to siding around building. This will lead to premature siding wear, moisture problems within wall, and creates an easy
path for wood destroying insects to enter home. Recommend trimming back all vegetation at least 12" to avoid associated damages. None
visible during time of inspection.
2.1 Item 9(Picture) - Vegetation on East side
2.1 Item 10(Picture) - Vegetation at NE corner of building
|
|
(3) Ivy growth around building This crawls under siding and gets into home. . Recommend removing to reduce associated underlying damages.
None visible during time of inspection.
2.1 Item 11(Picture) - Ivy growth on West side of building
|
2.2 |
WINDOWS
Comments: Maintenance Item. |
Peeling paint and rot at window frames and sills around building. Recommend properly repairing and repainting to avoid continued damage
to underlying framing areas. No underlying moisture damages visible during time of inspection.
2.2 Item 1(Picture) - Rot and peeling paint on East side of building
2.2 Item 2(Picture) - Rot and peeling paint at West side windows
|
2.3 |
WINDOW WELLS
Comments: Inspected. Appears Good Or In Working Condition. |
2.4 |
EXTERIOR DOORS
Comments: Safety Item. |
11260/11258/11266 - Patio has big step into home. Maximum height should be 8" (step is currently 12" high). Recommend adding
intermediate step to avoid associated tripping hazard.
2.4 Item 1(Picture) - Large step into 11260
2.4 Item 2(Picture) - Large step into 11258
2.4 Item 3(Picture) - Large step into 11266
|
2.5 |
EXTERIOR LIGHTING
Comments: Inspected. Appears Good Or In Working Condition. |
2.6 |
OTHER DISCOVERIES
Comments: Not Present. |
Cooling Unit Type:
A/C |
Temperature Differential:
18-22 DEG. |
Cooling Unit Manufacturer:
BRYANT CARRIER NORDYNE YORK |
Cooling Unit Age:
APPROX. 4 11 12 18 30 |
3.0 |
COMPRESSOR UNIT
Comments: Specialist Item. |
(1) 11256/11262/11264/11266 - Outdoor unit is not level. Excessive movement can crack HP/LP tubing at connections. Unit works as intended
during time of inspection, but recommend bringing unit to within 1 inch of level to maintain proper performance.
3.0 Item 1(Picture) - 11256 condenser unit not level
3.0 Item 2(Picture) - 11262 condenser not level
3.0 Item 3(Picture) - 11264 condenser is not level
3.0 Item 4(Picture) - 11266 A/C condenser is not level
|
|
(2) 11256 - Outdoor unit is 18 years old, rusty, and nearing the end of its useful life. It operates as intended during time of inspection; however,
recommend servicing to maximize performance. Additionally, recommend providing annual system maintenance to maximize efficiency and
extend useful life. Budget for replacement.
3.0 Item 5(Picture) - 11256 condenser is 18 years old and rusty
|
|
(3) 11258 - Dirty fins at exterior condenser unit. Recommend cleaning (spray off with hose) to maximize life and efficiency. Unit operates
properly during time of inspection.
3.0 Item 6(Picture) - Dirty fins at 11258 condenser unit
|
|
(4) 11262/11264 - Broken electrical conduit at condenser unit. This makes wiring vulnerable to inadvertent damage. Recommend contracting
professional HVAC technician to repair to maintain associate safe and proper performance. Unit operates properly during time of inspection.
3.0 Item 7(Picture) - Broken conduit at 11262 A/C
3.0 Item 8(Picture) - Broken conduit at 11264 A/C unit
|
|
(5) 11264 - Outdoor unit is approx. 30 years old, rusty, and nearing the end of its useful life. It operates as intended during time of inspection; however, recommend servicing to maximize performance. Additionally, recommend providing annual system maintenance to maximize efficiency and extend useful life. Budget to replace. | |
(6) 11264 - Damaged fins at exterior condenser unit. Recommend contracting licensed HVAC technician to repair to maintain proper condenser
performance. Unit operates properly during time of inspection.
3.0 Item 9(Picture) - Dirty fins at 11264 condenser unit
|
|
(7) 11266 - Soil has been built up around compressor unit. Recommend removing to avoid deterioration and associated damages. None visible
during time of inspection.
3.0 Item 10(Picture) - Soil up around 11266 A/C unit
|
|
(8) 11266 - Outdoor unit is damaged. It appears unit has been hit with lawn mower. Recommend repairing to maintain proper performance.
Unit operates properly during time of inspection.
3.0 Item 11(Picture) - 11266 A/C is damaged
|
3.1 |
REFRIGERANT LINES
Comments: Specialist Item. |
(1) 11258 - A/C refrigerant lines have iced up at condenser. This is often caused by low refrigerant, a clogged filter, or a clogged evaporator
coil. Recommend contracting professional HVAC contractor to evaluate and repair to maintain proper system performance. A/C is blowing
warm during time of inspection.
3.1 Item 1(Picture) - Refrigerant lines have iced up
|
|
(2) 11260/11262 - Worn and deteriorated insulation at A/C refrigerant line. This will lower overall efficiency of system. Recommend repairing to
ensure maximum efficiency.
3.1 Item 2(Picture) - Worn insulation at 11260 refrigerant lines
3.1 Item 3(Picture) - Missing insulation in at 11262
|
3.2 |
EVAPORATOR UNIT
Comments: Specialist Item. |
(1) 11258 - Evaporator is actively leaking behind furnace enclosure. This is often caused by cracked pan or clogged drain. If left unattended,
this condition may ultimately crack the heat exchanger and cause premature furnace replacement. Recommend contracting licensed HVAC
technician to repair to maximize remaining life and system performance. No significant damages visible during time of inspection.
3.2 Item 1(Picture) - 11258 evaporator is leaking behind furnace
|
|
(2) 11256 - Evaporator is actively leaking on top of furnace enclosure. This is often caused by cracked pan or clogged drain. If left unattended,
this condition may ultimately crack the heat exchanger and cause premature furnace replacement. Recommend contracting licensed HVAC
technician to repair to maximize remaining life and system performance. No significant damages visible during time of inspection.
3.2 Item 2(Picture) - Evaporator leakage on top of 11256
|
3.3 |
AIR DISTRIBUTION SYSTEM
Comments: Inspected. Appears Good Or In Working Condition. |
3.4 |
NORMAL OPERATING CONTROLS
Comments: Not Inspected. |
Viewed Roof Covering From:
GROUND ROOF EDGE |
Limitations:
HEIGHT |
Roof Type:
GABLE |
Age Of Shingles:
4 |
Roof Pitch:
4-12 |
Number Of Layers:
1 |
Fascia / Soffit:
WOOD |
Roof Covering:
ASPHALT/FIBERGLASS |
Life Expectancy:
NEARING MIDDLE |
4.0 |
GUTTERS, DOWNSPOUTS, AND DRAINAGE
Comments: Maintenance Item. |
Downspout drains water too close to foundation on East side of building. Recommend extending at least 6' away from foundation wall to
avoid possibility of moisture penetration and associated damages. None visible during time of inspection.
4.0 Item 1(Picture) - Extend downspout on East side
|
4.1 |
SOFFITS AND FASCIAS
Comments: Maintenance Item. |
Peeling paint and rot soffit/fascia boards around building. Recommend properly repairing and repainting all damaged areas to extend their
useful life. No significant damages visible during time of inspection.
4.1 Item 1(Picture) - Peeling paint on East side
4.1 Item 2(Picture) - Peeling paint above 11260
4.1 Item 3(Picture) - Rot in soffit on West side
4.1 Item 4(Picture) - Hole in soffit at SW corner of roof
4.1 Item 5(Picture) - Rot and peeling paint on West side
4.1 Item 6(Picture) - Rot at 11264 Soffit on West side
4.1 Item 7(Picture) - Peeling paint and rot on South side
|
4.2 |
ROOF COVERINGS
Comments: Inspected. Appears Good Or In Working Condition. |
4.3 |
ROOF VENTILATION
Comments: Inspected. Appears Good Or In Working Condition. |
4.4 |
FLASHINGS
Comments: Inspected. Appears Good Or In Working Condition. |
4.5 |
SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS
Comments: Inspected. Appears Good Or In Working Condition. |
Method Used To Observe Attic:
FROM ENTRY |
Limitations:
INSULATION |
Roof Structure:
PLYWOOD WOOD RAFTER |
Attic Insulation:
BLOWN FIBERGLASS |
Ventilation:
GABLE END ROOF |
5.0 |
ROOF STRUCTURE
Comments: Maintenance Item. |
11266 - Split roof rafter visible on South side of attic. This indicates possible point of weakness. Recommend properly repairing to maintain
designed weight bearing capacity to roof structure. No underlying structural damages visible during time of inspection.
5.0 Item 1(Picture) - Split roof rafter in 11266 attic
|
5.1 |
INSULATION
Comments: Maintenance Item. |
11262 - 3 inches of blown fiberglass insulation present. U.S. Department of Energy recommends R-38 rating in attic spaces, which equates
to 13 inches. Consider providing additional depth to maintain intended energy efficiency to home and reduce associated fuel costs.
5.1 Item 1(Picture) - 3 inches of blown fiberglass insulation in all attics
|
5.2 |
ATTIC ACCESS
Comments: Inspected. Appears Good Or In Working Condition. |
5.3 |
VENTILATION, FANS, AND EXHAUST DUCTING
Comments: Inspected. Appears Good Or In Working Condition. |
5.4 |
SKYLIGHTS, CHIMNEYS, AND ROOF PENETRATIONS ( ATTIC VIEW)
Comments: Inspected. Appears Good Or In Working Condition. |
5.5 |
CIRCUIT WIRING
Comments: Inspected. Appears Good Or In Working Condition. |
Much of circuit wiring concealed beneath insulation, limiting degree of visual inspection. All reported conditions based upon visually verifiable areas. |
Floor:
CARPET |
Wall:
DRYWALL |
Ceiling:
DRYWALL |
Windows:
ALUMINUM SINGLE HUNG |
Door:
WOOD HINGED |
Closet / Door:
METAL WOOD FOLDING SLIDING ATTIC ACCESS |
6.0 |
FLOOR
Comments: Inspected. Appears Good Or In Working Condition. |
6.1 |
WALLS
Comments: Inspected. Appears Good Or In Working Condition. |
6.2 |
CEILING
Comments: Inspected. Appears Good Or In Working Condition. |
6.3 |
WINDOWS
Comments: Maintenance Item. |
(1) 11262 - Window missing latch on North bedroom. Recommend installing to provide intended security protection to home. | |
(2) 11262 - Window assist/lift components are not working properly in South bedroom (window will not stay up). Recommend repairing to restore proper window performance. |
6.4 |
DOOR
Comments: Inspected. Appears Good Or In Working Condition. |
6.5 |
CLOSET/DOOR
Comments: Inspected. Appears Good Or In Working Condition. |
6.6 |
LIGHTING
Comments: Maintenance Item. |
11266 - Light out. Replace bulb. If this does not correct, recommend contracting electrician to investigate and correct to restore safe and proper operation. |
6.7 |
RECEPTACLES AND SWITCHES
Comments: Inspected. Appears Good Or In Working Condition. |
6.8 |
HEAT SOURCE
Comments: Inspected. Appears Good Or In Working Condition. |
6.9 |
SMOKE DETECTOR
Comments: Safety Item. |
11262/11266/11264/11260 - Smoke detectors missing in ALL bedrooms. Installation necessary to provide necessary early fire/smoke detection to spaces. |
Exhaust Fan Type:
FAN WITH LIGHT |
Floor:
VINYL |
Wall:
DRYWALL |
Ceiling:
DRYWALL |
Windows:
ALUMINUM SINGLE HUNG |
Vanity / Cabinetry / Countertops:
LAMINATE WOOD CABINET |
Tub Enclosure:
CERAMIC TILE PLASTIC ENCLOSURE |
GFCI Protection:
IN SAME SPACE |
7.0 |
FUNCTIONAL FLOW
Comments: Inspected. Appears Good Or In Working Condition. |
7.1 |
FLOOR
Comments: Maintenance Item. |
11260 - Missing caulking at base of tub enclosure. Recommend properly sealing to reduce possible moisture penetration and associated
damages. Floor is soft and slopes toward tub during time of inspection.
7.1 Item 1(Picture) - Missing caulking at 11260 floor
|
7.2 |
WALLS
Comments: Maintenance Item. |
11266 - Superficial mold growth visible at upstairs bathroom wall, but no moisture detected during time of inspection. This appears to be
caused from active moisture leaks within bathroom. Recommend cleaning wall to avoid associated moisture damage. None visible during
time of inspection.
7.2 Item 1(Picture) - Superficial mold in 11266 bathroom wall
|
7.3 |
CEILING
Comments: Maintenance Item. |
11264 - Old moisture stains visible at half bath ceiling, but no moisture detected during time of inspection. This appears to be caused from
overflow or leak at hall bath, above. Recommend properly sealing and painting to avoid future moisture damage. No underlying damages
visible during time of inspection.
7.3 Item 1(Picture) - Old moisture stains in 11264 half bath ceiling
|
7.4 |
WINDOW
Comments: Inspected. Appears Good Or In Working Condition. |
7.5 |
DOOR
Comments: Inspected. Appears Good Or In Working Condition. |
7.6 |
LIGHTING
Comments: Specialist Item. |
(1) 11262/11260 - Lighting is on GFCI circuit in main floor half bath. This is improper since lights will not work if GFCI circuit is tripped. Recommend contracting professional electrician to place lights on dedicated circuit to maintain constant, reliable function. | |
(2) 11264 - Light out in half bath. Replace bulb. If this does not correct, recommend contracting electrician to investigate and correct to restore safe and proper operation. |
7.7 |
RECEPTACLES AND SWITCHES
Comments: Inspected. Appears Good Or In Working Condition. |
7.8 |
EXHAUST FAN
Comments: Not Present. |
7.9 |
SINK, FAUCET, PLUMBING, AND TRAP DRAIN
Comments: Not Present., Maintenance Item. |
(1) 11262 - Active leakage at sink basin in upstairs bath. Recommend properly repairing to avoid further leakage and associated moisture
damages. No significant damages visible during time of inspection.
7.9 Item 1(Picture) - Leak at 11262 sink basin
|
|
(2) 11266 - Faucet leaks in upstairs bath. Recommend repairing to restore operation. | |
(3) 11264 - Faucet is loose in half bath. . Recommend properly securing to avoid any possible inadvertent piping damages during use. None visible during time of inspection. | |
(4) 11260 - Active leakage beneath both sinks. Recommend properly repairing to avoid further leakage and associated moisture damages.
Moisture damages visible beneath left sink during time of inspection.
7.9 Item 2(Picture) - Active leak beneath both sink in 11260 upstairs bath
|
|
(5) Slow drain at left sink. Recommend cleaning to restore proper drainage. If this does not correct, contract plumber to investigate and repair to avoid possible overflow. No associated damages visible during time of inspection. |
7.10 |
VANITY, CABINETRY, AND COUNTERTOPS
Comments: Inspected. Appears Good Or In Working Condition. |
7.11 |
TOILET
Comments: Maintenance Item. |
(1) 11262 - Upstairs toilet is loose and leaking. Recommend properly repairing to avoid future damages to underlying framing members. Unable
to determine extent of underlying damages during time of inspection.
7.11 Item 1(Picture) - Leakage at 11262 upstairs toilet
|
|
(2) 11262/11266/12258 - Half bath toilet is loose. This condition will eventually worsen and leak if not repaired. Recommend properly securing to avoid future leakage and associated damages. None visible during time of inspection. | |
(3) 11266/11264/11260/11258/11256 - Upstairs toilet is loose. This condition will eventually worsen and leak if not repaired. Recommend properly securing to avoid future leakage and associated damages. None visible during time of inspection. | |
(4) 11264 - Toilet flush handle is broken in half bath. Recommend repairing to restore proper operation. | |
(5) 11260 - Half bath toilet is loose and leaking. Recommend properly repairing to avoid further leakage and associated moisture damages. Unable to determine extent of underlying damages during time of inspection. |
7.12 |
TUB AND ENCLOSURE
Comments: Maintenance Item. |
(1) 11262 - Loose shower head piping and faucet in upstairs bath. Recommend properly securing to avoid possible leakage due to movement. None visible during time of inspection. | |
(2) 11262 - Tub faucet is leaking. Recommend repairing to restore proper operation. | |
(3) 11264 - Deteriorated caulking at base of tub enclosure. Recommend properly recaulking to reduce possible moisture penetration and
associated damages. None visible during time of inspection.
7.12 Item 1(Picture) - Deteriorated caulking at base of 11264 tub enclosure
|
|
(4) 11260/11256 - Loose shower head piping. Recommend properly securing to avoid possible leakage due to movement. None visible during time of inspection. | |
(5) 11258 - Faucet diverter is stuck closed (only shower works). Recommend repairing to restore proper operation. |
7.13 |
HEAT SOURCE
Comments: Inspected. Appears Good Or In Working Condition. |
Floor:
CARPET TILE WOOD |
Walls:
DRYWALL |
Ceiling:
DRYWALL |
Windows:
ALUMINUM SINGLE HUNG |
Stairway / Railing:
CARPET METAL RAILING |
Front Door:
METAL CLAD DEADBOLT |
8.0 |
FLOORS
Comments: Inspected. Appears Good Or In Working Condition. |
8.1 |
WALLS
Comments: Inspected. Appears Good Or In Working Condition. |
8.2 |
CEILINGS
Comments: Inspected. Appears Good Or In Working Condition. |
8.3 |
WINDOWS
Comments: Inspected. Appears Good Or In Working Condition. |
8.4 |
LIGHTING
Comments: Inspected. Appears Good Or In Working Condition. |
8.5 |
RECEPTACLES AND SWITCHES
Comments: Inspected. Appears Good Or In Working Condition. |
8.6 |
STAIRWAY AND RAILING
Comments: Inspected. Appears Good Or In Working Condition. |
8.7 |
FRONT DOOR
Comments: Maintenance Item. |
11266 - Deteriorated weatherstripping around front door. Recommend repairing to reduce possible moisture penetration and increase energy
efficiency to space.
8.7 Item 1(Picture) - Deteriorated caulking around 11266 front door
|
8.8 |
SMOKE/CO DETECTORS
Comments: Safety Item. |
11258/11256 - Smoke detector missing in upstairs hallway. Installation necessary to provide necessary early fire/smoke detection to space. |
Floor Covering:
TILE WOOD |
Walls:
DRYWALL |
Ceiling:
DRYWALL |
Windows:
ALUMINUM SINGLE HUNG SLIDING |
Cabinetry:
WOOD |
Countertop:
LAMINATE |
Patio Door:
METAL VINYL SLIDING |
Disposer:
BADGER |
Dishwasher:
WHIRLPOOL |
Range / Oven / Cooktop:
WHIRLPOOL |
Exhaust / Range Hood:
BROAN |
Refrigerator:
HOTPOINT |
GFCI Protection:
IN SAME SPACE |
9.0 |
FLOOR
Comments: Inspected. Appears Good Or In Working Condition. |
9.1 |
WALLS
Comments: Inspected. Appears Good Or In Working Condition. |
9.2 |
CEILING
Comments: Specialist Item. |
11262 - Moisture stains and damages visible at ceiling. This appears to be caused from active leakage at toilet in hall bath, above.
Recommend hiring professional roofing contractor to investigate and repair to avoid continued moisture damages. Unable to determine
extent of underlying damages during time of inspection.
9.2 Item 1(Picture) - Active leakage in 11262 kitchen ceiling
|
9.3 |
WINDOWS
Comments: Inspected. Appears Good Or In Working Condition. |
9.4 |
PATIO DOOR
Comments: Inspected. Appears Good Or In Working Condition. |
9.5 |
LIGHTING
Comments: Inspected. Appears Good Or In Working Condition. |
9.6 |
CEILING FAN
Comments: Inspected. Appears Good Or In Working Condition. |
9.7 |
RECEPTACLES AND SWITCHES
Comments: Safety Item. |
11264/11260/11256 - No GFCI protection to the left of sink. Recommend installing to provide necessary electrical safety protection to circuit. |
9.8 |
SINK, FAUCET, PLUMBING, AND TRAP DRAIN
Comments: Maintenance Item. |
11264 - Active leakage beneath sink. Recommend properly repairing to avoid further leakage and associated moisture damages. No
significant damages visible during time of inspection.
9.8 Item 1(Picture) - Active leakage beneath 11264 kitchen sink
|
9.9 |
CABINETS AND COUNTERTOPS
Comments: Inspected. Appears Good Or In Working Condition. |
9.10 |
FOOD WASTE DISPOSER
Comments: Inspected. Appears Good Or In Working Condition. |
9.11 |
DISHWASHER
Comments: Inspected. Appears Good Or In Working Condition. |
9.12 |
STOVE/OVEN/COOKTOP
Comments: Inspected. Appears Good Or In Working Condition. |
9.13 |
RANGE HOOD
Comments: Maintenance Item. |
11264/11260 - Light is out. Replace bulb. If this does not correct, recommend contracting electrician to investigate and repair as necessary to restore proper operation. |
9.14 |
REFRIGERATOR
Comments: Inspected. Appears Good Or In Working Condition. |
9.15 |
HEAT SOURCE
Comments: Inspected. Appears Good Or In Working Condition. |
9.16 |
SMOKE/CO DETECTOR
Comments: Not Present. |
Floor:
CARPET |
Walls:
DRYWALL |
Ceiling:
DRYWALL |
Windows:
ALUMINUM SINGLE HUNG SLIDING |
Patio Door:
METAL SLIDING |
10.0 |
FLOOR
Comments: Inspected. Appears Good Or In Working Condition. |
10.1 |
WALLS
Comments: Inspected. Appears Good Or In Working Condition. |
10.2 |
CEILING
Comments: Inspected. Appears Good Or In Working Condition. |
10.3 |
WINDOWS
Comments: Inspected. Appears Good Or In Working Condition. |
10.4 |
PATIO DOOR
Comments: Maintenance Item. |
11266 - Active leakage around patio door. Recommend hiring professional contractor to evaluate and repair to maintain proper performance. Unable to determine extent of underlying damages during time of inspection. |
10.5 |
LIGHTING
Comments: Not Present. |
10.6 |
RECEPTACLES AND SWITCHES
Comments: Inspected. Appears Good Or In Working Condition. |
10.7 |
HEAT SOURCE
Comments: Inspected. Appears Good Or In Working Condition. |
10.8 |
SMOKE/CO DETECTORS
Comments: Not Present. |
Floor:
WOOD |
Walls:
DRYWALL |
Ceiling:
DRYWALL |
Patio Door:
VINYL SLIDING |
11.0 |
FLOOR
Comments: Inspected. Appears Good Or In Working Condition. |
11.1 |
WALLS
Comments: Inspected. Appears Good Or In Working Condition. |
11.2 |
CEILING
Comments: Inspected. Appears Good Or In Working Condition. |
11.3 |
PATIO DOOR
Comments: Inspected. Appears Good Or In Working Condition. |
11.4 |
LIGHTING
Comments: Maintenance Item. |
11266 - Light out. Replace bulb. If this does not correct, recommend contracting electrician to investigate and correct to restore safe and proper operation. |
11.5 |
CEILING FAN
Comments: Inspected. Appears Good Or In Working Condition. |
11.6 |
RECEPTACLES AND SWITCHES
Comments: Inspected. Appears Good Or In Working Condition. |
11.7 |
HEAT SOURCE
Comments: Inspected. Appears Good Or In Working Condition. |
11.8 |
SMOKE/CO DETECTORS
Comments: Not Present. |
Limitations:
HEAVY CLUTTER AND STORAGE ITEMS HVAC DUCTING PLUMBING COMPONENTS |
Floor:
CONCRETE |
Foundation / Wall:
POURED CONCRETE |
Ceiling:
UNFINISHED |
Vents / Windows:
ALUMINUM SLIDING |
Columns / Beams / Posts:
METAL BEAM METAL POST |
Rim / Floor Joists:
WOOD |
12.0 |
BASEMENT STAIRWAY AND RAILING
Comments: Safety Item. |
11264 - Missing handrail at basement steps. Recommend installing to provide necessary stability during use.
12.0 Item 1(Picture) - Missing handrail at 11264 basement steps
|
12.1 |
FLOOR
Comments: Inspected. Appears Good Or In Working Condition. |
12.2 |
FOUNDATION / WALLS
Comments: Specialist Item. |
(1) 11266 - Settlement cracking visible on East side of basement. Previous repairs do not appear to have been successful since subsequent
movement is visible. Recommend hiring professional foundation contractor to properly repoint to avoid further deterioration and possible
moisture seepage. None visible during time of inspection.
12.2 Item 1(Picture) - Settlement crack in 11266 foundation wall
|
|
(2) 11256 - Superficial mold visible on wall. This is likely due to basement bring dark and dryer venting into space. Recommend cleaning wall
and installing dehumidifier within basement to avoid associated health hazards. No moisture damages visible during time of inspection.
12.2 Item 2(Picture) - Mold on walls in 11256 basement
12.2 Item 3(Picture) - More mold in 11256 basement
12.2 Item 4(Picture) - And more superficial mold in 11256 basement
|
12.3 |
CEILING / SUB-FLOOR
Comments: Specialist Item. |
(1) 11260 - Moisture damages visible at sub-floor beneath half bath toilet. Recommend hiring professional contractor to evaluate and repair to
avoid further leakage and associated damages. No significant damages visible during time of inspection.
12.3 Item 1(Picture) - Active leakage beneath 11260 half bath toilet
|
|
(2) 11260 - Daylight visible through sub floor on South side of basement. Recommend hiring professional contractor to investigate and repair to
avoid continued damage to underlying framing members. No significant damages visible during time of inspection.
12.3 Item 2(Picture) - Daylight through 11260 rim joist
|
12.4 |
RIM/FLOOR JOISTS
Comments: Inspected. Appears Good Or In Working Condition. |
12.5 |
VENTS OR WINDOWS
Comments: Inspected. Appears Good Or In Working Condition. |
12.6 |
DOORS
Comments: Inspected. Appears Good Or In Working Condition. |
12.7 |
LIGHTING
Comments: Inspected. Appears Good Or In Working Condition. |
12.8 |
RECEPTACLES AND SWITCHES
Comments: Inspected. Appears Good Or In Working Condition. |
12.9 |
CIRCUIT WIRING
Comments: Inspected. Appears Good Or In Working Condition. |
12.10 |
COLUMNS, BEAMS, OR POSTS
Comments: Inspected. Appears Good Or In Working Condition. |
12.11 |
HEAT SOURCE
Comments: Inspected. Appears Good Or In Working Condition. |
12.12 |
SMOKE / CO DETECTORS
Comments: Safety Item. |
11256 - Smoke detector missing. Installation necessary to provide necessary early fire/smoke detection to space. |
Floor:
VINYL |
Walls:
DRYWALL |
Ceiling:
DRYWALL |
Dryer Energy Source:
220V 3-PRONG |
Dryer Vent Termination:
EXTERIOR |
13.0 |
FLOOR
Comments: Inspected. Appears Good Or In Working Condition. |
13.1 |
WALLS
Comments: Inspected. Appears Good Or In Working Condition. |
13.2 |
CEILING
Comments: Inspected. Appears Good Or In Working Condition. |
13.3 |
LIGHTING
Comments: Inspected. Appears Good Or In Working Condition. |
13.4 |
RECEPTACLES AND SWITCHES
Comments: Inspected. Appears Good Or In Working Condition. |
13.5 |
TRAP/DRAIN
Comments: Inspected. Appears Good Or In Working Condition. |
13.6 |
HEAT SOURCE
Comments: Inspected. Appears Good Or In Working Condition. |
13.7 |
SMOKE DETECTOR
Comments: Not Present. |
Location of Thermostat:
HALLWAY |
Heat Type:
FORCED AIR |
Fuel Source:
NATURAL GAS |
Filter Type:
DISPOSABLE |
Heating Unit Manufacturer:
INTERTHERM NORDYNE RHEEM WEATHERKING |
Heating Unit Age:
12 13 20 |
Input BTUH:
72000 75000 96000 |
14.0 |
ENERGY SOURCE
Comments: Inspected. Appears Good Or In Working Condition. |
14.1 |
HEATING EQUIPMENT
Comments: Maintenance Item. |
(1) 11262/11260/11256 - Furnace is 20 years old (expected life is 20-25 years) and displays heavy rust and corrosion in burner/heat exchanger
areas. Unable to determine extent of underlying damages, but unit performs as intended during time of inspection. Recommend having unit
serviced regularly to maximize life and system efficiency. Budget for future replacement.
14.1 Item 1(Picture) - Rust and corrosion in 11262 furnace
14.1 Item 2(Picture) - Rust and corrosion inside 11260 furnace
14.1 Item 3(Picture) - Rust and corrosion inside 11256 furnace
|
|
(2) 11258 - Furnace is 37 years old (expected life is 20-25 years) and displays heavy rust, corrosion, and sediment build-up in
burner/blower/heat exchanger areas. Unable to determine extent of underlying damages, but unit performs as intended during time of
inspection. Recommend having unit serviced regularly to maximize life and system efficiency. Budget for future replacement.
14.1 Item 4(Picture) - View inside 11258 furnace
|
14.2 |
NORMAL OPERATING CONTROLS
Comments: Inspected. Appears Good Or In Working Condition. |
14.3 |
AUTOMATIC SAFETY CONTROLS
Comments: Inspected. Appears Good Or In Working Condition. |
14.4 |
CHIMNEYS, FLUES AND VENTS
Comments: Maintenance Item. |
(1) 11262 - HVAC supply vent is disconnected within basement. Recommend properly sealing with metallic tape to maximize system
efficiency.
14.4 Item 1(Picture) - Vent disconnected inside 11262 basement
|
|
(2) 11262 - Duct tape used to seal seams at HVAC vents. This is improper and tape will ultimately become dry and brittle. Recommend
properly sealing all open seams with metal tape then properly insulating ducting to maximize flow and efficiency to home.
14.4 Item 2(Picture) - Duct tape at vents in 11262 basement
|
|
(3) 11266 - Open seams at HVAC exhaust vent above furnace. This is a health hazard since dangerous flue gases can escape into home.
Recommend properly sealing all open seams with metal tape to maximize draw and maintain safe furnace operation.
14.4 Item 3(Picture) - Open seams at 11266 furnace exhaust vent
|
14.5 |
HEAT DISTRIBUTION SYSTEM
Comments: Inspected. Appears Good Or In Working Condition. |
14.6 |
HEAT SOURCE IN EACH LIVING SPACE
Comments: Inspected. Appears Good Or In Working Condition. |
14.7 |
SMOKE/CO DETECTORS IN SPACE
Comments: Safety Item. |
11262/11266/11264/11260/11258/11256 - No CO detector present in rooms with fuel burning appliances. A CO detector should be installed in same space as all fuel-burning appliances (not directly above or beside units since it is normal for them to emit a small amount of carbon monoxide upon start-up) and in all upper-level hallways. Recommend installing to provide early CO detection to occupants and avoid associated personal safety hazards |
14.8 |
FURNACE ENCLOSURE
Comments: Maintenance Item. |
11262/11264/11260 - Air leaks at seams around furnace enclosure. This is inefficient. Recommend sealing all leaks with metallic tape to
maximize system efficiency and improve performance.
14.8 Item 1(Picture) - Air leaks around 11262 furnace enclosure
14.8 Item 2(Picture) - Air leaks around 11264 furnace enclosure
14.8 Item 3(Picture) - Air leak at 11260 refrigerant lines
|
Water Main Location:
BASEMENT |
Water Source:
PUBLIC |
Hose Bibs:
FROST FREE |
Plumbing Service:
COPPER |
Plumbing Distribution:
COPPER |
Plumbing Waste:
PVC |
Water Heater Manufacturer:
A.O. SMITH U.S. CRAFTMASTER WHIRLPOOL |
Water Heater:
NATURAL GAS 40 GAL. (1-2 PEOPLE) |
Water Heater Age:
10 12 13 17 |
15.0 |
MAIN WATER SUPPLY
Comments: Specialist Item. |
11256 - Active leakage in pressure reducing valve. Recommend contracting plumber to evaluate and repair to avoid continued leakage and
possible moisture damage. None visible during time of inspection.
15.0 Item 1(Picture) - Active leak at 11256 pressure reducing valve
|
15.1 |
MAIN WATER SHUT-OFF
Comments: Maintenance Item. |
11262/11260 - Active leakage in water main valve. Recommend contracting professional plumber to evaluate and repair to avoid continued
leakage and possible moisture damage. None visible during time of inspection.
15.1 Item 1(Picture) - Active leakage at 11262 water main
15.1 Item 2(Picture) - Active leakage at 11260 water main
|
15.2 |
HOSE BIBS
Comments: Inspected. Appears Good Or In Working Condition. |
15.3 |
DISTRIBUTION PIPING
Comments: Specialist Item. |
11262 - Copper plumbing is in contact with galvanized HVAC ducting. This will lead to galvanic corrosion and leakage. Recommend
contracting professional plumber to evaluate and relocate to avoid possible moisture damages. None visible during time of inspection.
15.3 Item 1(Picture) - Water lines touch galvanized ducting in 11262 basement
|
15.4 |
INTERIOR DRAIN, WASTE AND VENT SYSTEMS
Comments: Inspected. Appears Good Or In Working Condition. |
15.5 |
FUEL DISTRIBUTION SYSTEMS
Comments: Specialist Item. |
11260 - No dirt leg present on natural gas supply line to water heater. This is piping component is necessary to keep natural gas clean and
extend life of associated gas appliances. Recommend installing to maximize useful life. See attached photo at bottom of report for a
detailed view.
15.5 Item 1(Picture) - No dirt leg at 11260 water heater
|
15.6 |
WATER HEATER
Comments: Maintenance Item. |
(1) 11262/11266/11264/11260/11258/11256 - Active leakage at drip tube. This can be caused by high tank pressure or sediment beneath valve
seat. Recommend contracting professional plumber to evaluate and repair to restore proper performance. No associated damages visible
during time of inspection.
15.6 Item 1(Picture) - Active leak at 11262 water heater relief valve
15.6 Item 2(Picture) - Active leak at 11266 relief valve
15.6 Item 3(Picture) - Active leak at 11264 relief valve
15.6 Item 4(Picture) - Active leak at 11260 relief valve
15.6 Item 5(Picture) - Active leak at 11258 relief valve
|
|
(2) 11262/11258 - Rust and corrosion in and around water heater. Units are 13 & 8 years old and operate as intended during time of
inspection. These conditions and its age (typical life of water heater is 10-12 years) indicate unit is at the end of its useful life. Budget for
replacement.
15.6 Item 6(Picture) - Rust at base of 11262 water heater
15.6 Item 7(Picture) - Corrosion on top of 11258 water heater
|
|
(3) 11262 - Glass view port is broken. This will affect water heater efficiency and performance. Recommend hiring professional plumber to
evaluate and repair to restore safe and proper operation.
15.6 Item 8(Picture) - Broken glass at 11262 water heater
|
|
(4) 11266 - Rust and corrosion in and around water heater. Unit is 17 years old and operates as intended during time of inspection. These
conditions and its age (typical life of water heater is 10-12 years) indicate unit is at the end of its useful life. Budget to replace.
15.6 Item 9(Picture) - Rust around 11266 water heater
|
|
(5) 11260 - Active leakage at drain bibb. Recommend hiring professional plumber to evaluate and repair to reduce continued leakage and
associated moisture damages. Moisture damages visible during time of inspection.
15.6 Item 10(Picture) - Active leakage at 11260 drain bibb
|
Electrical Service:
UNDERGROUND ALUMINUM SERVICE CONDUCTORS 220 VOLTS |
Service Size:
100 AMP |
Circuit Protection:
CIRCUIT BREAKERS |
Main Panel Manufacturer:
ZINSCO |
Conductor Materials:
COPPER ROMEX |
Grounding:
WATER MAIN |
16.0 |
SERVICE ENTRANCE
Comments: Specialist Item. |
11256/11260 - Electrical service meter is pulling away from home. This is likely caused by grading settlement. Recommend contract local
utility to properly evaluate and repair to maintain reliable service and avoid possible damage. No significant damages visible during time of
inspection.
16.0 Item 1(Picture) - Loose meter at 11256
16.0 Item 2(Picture) - Loose meter at 11260
|
16.1 |
DISTRIBUTION PANEL
Comments: Maintenance Item. |
(1) 11262/11266/11264/11260/11258/11256 - Zinsco main distribution panel installed. These panels were originally made in Puerto Rico and
installed in the 60's and 70's throughout the USA. There are many still in use in both single-family and multi-family units. Zinsco sold
their manufacturing plants to Sylvania who then marketed them under the GTE Sylvania brand until finally closing down. Today, the
Zinsco name is owned by Thomas and Betts.
Major Problems: 1) It has been found that circuit breakers do not trip under normal overload conditions (It has been known to sometimes take up to 60-amps to trip a 15-amp Zinsco breaker. 2) The parallel flat buss bars are made of aluminum material and corrode quite easily, increasing the electrical resistance at point of contact and causing panels to overheat. 3) The plating that coats the buss bars sometimes fails on many Zinsco panels, causing poor circuit breaker connections. 4) Another problem is that the breakers do not have designated positions, i.e., they can slide up and down the buss bar, are often crooked, and it is not uncommon to see gaps between the breakers with the deadfront cover in place. Recommend monitoring panel for signs of overheating. No signs of past problems visible during time of inspection. 16.1 Item 1(Picture) - This is a Zinsco panel
|
|
(2) 11262 - 15-Amp circuit breaker in main panel would not reset (unable to turn breaker on) during time of inspection. Recommend contracting
electrician to investigate and repair to restore proper operation. Unable to pinpoint cause during time of inspection.
16.1 Item 2(Picture) - Breaker will not reset in 11262 panel
|
|
(3) 11262/11266 - Knockout missing. These are necessary to maintain designed electrical safety and avoid rodent intrusion. Recommend
contracting electrician to install and avoid associated electrical safety hazards.
16.1 Item 3(Picture) - Missing knockout at 11262 panel
16.1 Item 4(Picture) - Missing knockout at 11266 panel
|
|
(4) 11264/11256 - Double tapping present (2 circuits double tapped). This presents a possible overheating hazard. Contract professional
electrician to evaluate and correct to avoid associated electrical safety hazards and maintain proper system performance. No associated
damages visible during time of inspection.
16.1 Item 5(Picture) - Double tapped breaker inside 11264 panel
16.1 Item 6(Picture) - Double tapped breaker inside 11256 panel
|
|
(5) 11258 - Twistout missing. These are necessary to maintain designed electrical safety and avoid rodent intrusion. Recommend contracting
electrician to install and avoid associated electrical safety hazards.
16.1 Item 7(Picture) - Missing twistout in 11258 panel
|
16.2 |
CIRCUIT WIRING
Comments: Inspected. Appears Good Or In Working Condition. |
16.3 |
GROUNDING
Comments: Specialist Item. |
11266/11260/11256 - No main grounding conductor installed. Installation necessary to maintain electrical grounding protection to home. Contract licensed electrician to properly correct and restore electrical safety to system and occupants. |